Leslie Orm shows us how to deal with a common refrigeration TXV issue.
Read all the tech tips, take the quizzes
and find our handy calculators at https://www.hvacrschool.com/
Read all the tech tips, take the quizzes
and find our handy calculators at https://www.hvacrschool.com/
All right so arms gon na give us this little txt screen and Rusty power has beat so here's what you get a service call saying that the this particular case is not making temperature and being this is a produce case in its really wet environment. Take a look at this. This power head right here held the powder coating is starting to come loose once the integrity of that power coat powder coating has been compromised. It will be just a matter of time before the power head loses its charge.
It gets rusted out so two things right here that are low hanging fruit to see what's going on, if you're having problems not making tip on this case is check this screen the inside here. If that screen is good and being as this power heads like this, these power heads are very inexpensive. I'd go ahead and just change that thing because, as you can see, this is a forty three millimeter power head, so change that clean the screen - and I would bet bottom dollar that that will solve your refrigeration issues of this thing, not making ten.
Thank You Bryan
Like this episode
I cut a power head open. Those things are pretty thick under that powder coating. I think they tend to leak the bulb charge from under neath from the diaphragm.
"Low hanging fruit" in the produce case? Lol
It was the txv
Only if all txvโs were that easy to get to life would be better lol
Maybe wash out the case while your in there. Get the bottom pan and drains cleaned up good too. ๐๐โก๏ธ๐ Service area Orleans??