Bert and Sam teach a class about ductless system install and maintenance practices. They particularly focus on wall-mounted mini-splits and do some flaring and cleaning prep demonstrations.
When installing a ductless system, you will need to think about the placement of the head, condenser, drain, line set, and high-voltage components. Before installation, it is best to review the scope of work, make sure you have all the necessary supplies in your van, read the manufacturer's manual, determine the placement of the components, and communicate all necessary information to the customer. It is also important to have appropriate PPE for procedures like cleaning and drilling, and you'll want to make sure you don't strain yourself while you work.
Flare joints are prone to leaking if we don't thoroughly test them, so we need to make sure we make flare connections that are tight and have strong copper. Make sure the copper has been deburred after being cut to avoid causing turbulence in the lines or creating ridges and cracks. You also want to use a high-quality flaring tool, whether you use a flaring block or power flaring tool; that way, the flare should have the proper diameter and depth. When torquing the flare nut, use a torque wrench set to the proper specs for the best results.
All line sets should also be insulated, though some technicians have reported that some sheaths may contribute to premature leaking. Cork tape and thumb gum are also inadequate for insulating ductless line sets. Pressure testing is also critical for identifying leaks early on. You will want to coat the joints in a bubble solution, wait for a little while, and make sure you inspect each joint with a flashlight and a mirror to check for microbubbles. Vacuum practices are very similar to the best practices for traditional split A/C units and heat pumps. The decay test can also help you realize that a system has a leak.
Ductless mini-splits usually have a relatively small charge compared to other types of systems. Be sure to follow the manufacturer's instructions and account for line length when setting the charge. You'll also want to make sure your condensate disposal methods are appropriate and working properly at the end of the installation. Generally, you will use either a gravity drain or a condensate pump. In many cases, gravity drains are ideal because they are quiet, have little maintenance compared to pumps, and have a lower chance of causing damage indoors. Condensate pumps may be the only feasible option when the unit is on an interior wall.
When you close out an installation, be sure to explain the most important aspects of equipment and remote operation, maintenance expectations, and condensate pump noise levels to the customer.
Regularly maintained ductless systems often don't take long to maintain, but they need attention to that they don't smelly and dirty quite quickly. PMs require you to talk to the customer and work inside their home, so customer service is critical. Ask the customer about their system, go over the scope of work with them, and show care for their home by wearing shoe covers and placing down drop clothes.
The maintenance process can be broken down into roughly five stages: pre-inspection, communicating issues, cleaning, confirming operation non-invasively, and having a closing conversation with the customer about what you did.
Before testing the system, let it run for at least 10 minutes. Then, do non-invasive testing, including checking the delta T. Watch out for things like low suction, ice on the expansion line, low split, or sloshing noises.
When it comes to cleaning, you will want to pull the filters and clean them with water. Try to wash condensers with water only unless they get impacted by soil, animal hair, or other debris. You'll probably have to expose the evaporator coil, drain pan, and blower wheel. You will likely need to remove the blower wheel for cleaning. When the evaporator coil is only a little bit dirty, you might use a rag or soft bristle brush, but you may need to clean the evaporator coil in place if there is significant soil. You can clean an evaporator coil in place using a bib kit.
To clean a gravity drain, flush and vacuum it and clean out the pan. You may need to remove the pan to access it. To clean a condensate pump, clean the reservoir, tubes, and screen, ensuring that the float is positioned correctly. Avoid using cleaners on pumps.
To finish up a maintenance job, make sure you leave the customer's home exactly how you found it. Check the make sure the system runs as it should. Communicate everything with the customer and allow them to raise questions or concerns.
Read all the tech tips, take the quizzes, and find our handy calculators at https://www.hvacrschool.com/.

Today's class is on ductless installation and maintenance, so we are not going to get into Super specifics here. We're going to sort of do an overview on some do's and don'ts some processes, but um, yeah, we'll just sort of jump right into it. So to start off, we have our class overview. We have our installation side, and then we have our maintenance side. To start off with our installation, we have our key points of installation. These are the points that we really want to slow down on with installation. Just like with anything else you do on a repeated process you get used to, it becomes sort of a rhythm. you sort of zone out, get comfortable with it. more of a muscle memory in some cases. but it's important to remember the key points. Those points that you want to slow down on because, uh, if you're not paying attention, they will bite you in the butt. So going over those key points, going over some best practices, whether it's pulling a vacuum or doing a pressure test, there's a right way to do something and a not so right way to do something. So here at Kalos we like to do it the right way. So that's right. that's right. So the best practices, so you know I don't have a ton of slides, so I'm going to spend extra long on all these here going over some common issues. We'd all liked our installation to go nice and smooth, but it never happens to go that way. So going over some common issues to expect and we're going to do some Hands-On demonstration up here pretty soon. But yeah, that'll be the installation side of things. Next, we have the ductless maintenance side. We're doing a step-by-step maintenance process. For those of us who have maintained regular split systems, it is a little bit different. so knowing where to start and where to end is important. Testing the equipment. For the most part it's It's pretty similar to a regular split. However, there are some steps you want to take in order to fully test the equipment. Drains like regular systems. we have the indoor unit that condensates water. That water goes somewhere. Where does it go? Well, it came to the right place. We'll be going over drains. We have pump maintenance. Uh, run into a lot of pumps. It's important to keep them clean maintained. Avoid issues. We have our blower wheel cleaning. There's a big difference between someone who knows how to do a cleaning and someone doesn't and that's 30 minutes and two hours. So knowing the right way to clean the blower wheel will help on efficiency and profitability, right? So pay attention to that part. And lastly, we have the coil cleaning with the bib kit. A lot of the ductless work we like to do is going to be non-invasive if possible light cleaning when we can, but in some cases they get pretty nasty, so being able to do that cleaning with the kit is going to be important. And then at the end we'll have some common customer issues and a little q. A All right Ductless Systems. We got a little quote here. man, nothing gets my big brain going like ductless systems. YOLO That was old Albert Einstein himself. Yeah, one of the best technicians in the field. but uh yeah, uh, you guys, it means you only live once. So that's my mindset with ductless units. But yeah, a lot of a lot of ductless units out there. Whether it be a, uh, a cassette in the ceiling, whether it be a pancake unit, a Vrf system stands for a variable refrigerant flow. Plenty of applications for them, However, today we are going to be going over one in particular and that's going to be the wall mount systems. It's the most used in residential for many reasons. They can be installed in bedrooms, enclosed, lanais. In some cases, multi-head units can be installed all across the house, so really nice units, Quiet, energy efficient, easy to maintain so customers love them for that reason and we are going to be focusing on that today. Components of the ductless Install: So we have our head unit here. It's where your evaporator, your blower motor, and where your drainage starts. So that's all located at the indoor unit. On the back side, we have our condenser. our pad. right? Is that wheel? is that locked or something? No, no, this is how it only turns. One Direction Oh, okay, so uh. Outdoor unit: We have our fan motor, outdoor coil, compressor, we have our Exv electronic expansion valve and then moving down the line. We do have our high voltage here, unlike a regular change out. A lot of these units are from the ground up installation, so we do have to run power from the breaker panel through the attic down to our condensing unit and then from our condensing unit to our indoor unit. So we have our high voltage and then we have our drain, whether it be a gravity drain or a pump of some style. So pre-installation Checklist: Before you actually go out and install one of these units, it's important to go over your checklist. So to start off, we want to review the scope of work before leaving the shop. So that's in the beginning with the Comfort advisor or the technician who was originally on site going over the equipment. Whether you're going to be looking at some photos or a site map, just having a full scope of the work before you actually leave the shop. Next is going to be reviewing the van stock and supplies. We want to avoid having to leave the job site for any reason to any supply houses or to the shop so making sure you're fully stocked up for the day? What are some common things that guys forget to have on their truck when they're going to go to a ductless install? Well, the most common things would be those materials that are regularly used such as refrigerant, line hide. Obviously, you shouldn't be leaving up behind the actual system itself or that's a problem. but any reusable materials capcoms, small stuff, insulation UV wrap. Just things that you're going to use on every install there adapters too. Yeah, all right. Once on site, you want to go over the full scope of work with the customer and review. The Proposal With the customer, it's important to remember that we are going to be spending all day at this house. A customer's home is their private safe spot and it's important that they trust you that you present yourself in a professional and clean manner, so that first that first 15 minutes are are important, you know you want to develop that relationship with them. It's the first time they've seen you, so introduce yourself, go over the full job, go over the equipment. It's important that everyone's on the same page as far as what's happening that day and what to expect. So that's that's sort of the overview of the full scope of work. And you're getting that, um, verbal approval that the condenser is going right here like this is what you talked about before just making sure that we're on the same page because you don't want to set something and then have a customer really care about after you've done all the work of placing somewhere actually. I wanted it six inches over here or something. So like this is going to go here And then the inside unit. Um, oh, you haven't gone from there yet? No, almost almost. Yeah. so the actual placements of the indoor and outdoor unit is important to go over. Um, indoor unit considerations. Is it on an interior wall? exterior wall? Um, you know the positives and the negatives of both of those. Um, you know where the hole is going to go if it's going to be an exterior wall and you're going to punch through what's on the other side of that? I'm just getting the full scope from beginning to end. so everyone's on the same page is important. So that's the inside and the outside lines and drain hole placement. And Pitch if it's going to be a gravity drain, Do we have enough space above the air handler to ceiling to actually have a gravity drain? We don't want to install unit and punch a four inch hole and find out we can't actually run a drain line there. so planning this all out will avoid some heartache. And last but not least, read the manual. Whether this is your first ductless installation or your 50th going through that manual, reading the specs, you know when they put this thing together, they weren't just throwing it together. they actually thought it through for the most part. So uh, knowing the radius is for the most part. knowing that like the back of your head is really important. so I recommend it. Also, you have the fact that we're mostly talking about the wall mount here, but like if you're doing a slightly different application than before, that's another important thing on the manual and then the manual for the service side. I Don't have a slide that says read the manual on the maintenance, but they have such fantastic manuals online. If it's like uh Mitsubishi you can go to my Link Drive and they have service manuals that tell you like where the screws are to take stuff apart like doesn't matter what you're replacing. it could be a board blower, motor wheel, coil, step-by-step process with pictures and those service manuals on like all your major ductless manufacturers. So yeah, we should have made a slide having that all up there. but you all get the idea so it doesn't matter if you're doing the install or you're doing maintenance. Like if you're doing maintenance work, you're working with cleaners and like something that's been in a customer's home so their dead skin cells are on that unit. Whatever it is, just protect your eyes and your hands. if you're working with cleaners and then on the install, you're doing a lot of heavy stuff and you get used to doing it every day so you can get more careless. but like there's drilling through the wall. um, safety considerations for yourself are really important. Also, when you go to drill a hole like what's what's on the other side here, Is there a breaker panel? Literally on the other side of this wall? No one would ever drill through that and hit a breaker panel? Yeah, so yeah. think about those things. Best practices and common issues I Sort of touched on those key points you always want to pay attention to. these are these are the key points here. So flares are a big one. Common callback are leaks on flare joints. They may look okay, but over time through vibration, expanding, and Contracting of copper, leaks do occur. so slowing down and following the correct process for that is important. Next one here, you have the pressure testing. Again, refer to the manual to what pressure the manufacturer recommends. a quick rule of thumb over 300 and under. You know, 600 is a good rule of thumb, but again, refer to that manual on that pressure test, setting the charge Like regular split units, these units do come pre-charged so uh, you know, knowing how much to add if any was going to be important. especially since they have such a low charge so we'll be going over that. and then again, drains and pumps are just some best practices with those. Some considerations with those All right, making flares and pressure testing. So here we have a couple slides on the proper way to to make a flare. Uh, just a few key things we want to point out here. Just to start off is the actual reaming process of deburring the inside of that copper. Whenever you use a copper cutter and you make the cut, you do get that lip on the inside. And if you don't deburr that lip, you tend to have a pretty bad flare. So we'll do a little demonstration here on the proper way to make a flare. Now there are a couple different tools you can use in these cases because these can cause such headaches. I Would recommend using the best tool in this slide. We obviously have a manual flare tool here for this demonstration. we will be using a battery operated flare toolkit. Really nice to have because they are pretty precise. There's not a lot of thinking you have to do with them, you just sort of clip it on and go to town. It's also worth mentioning this is not the uh, latest version of Navac. Claire They actually have two. Um, this is the earlier version, the newer one I Don't remember. Yeah, it's a little more. This is a little bit of a later, but this this one is actually really great. Still, it's really great. Yeah and it's still sold. The newer one can get into some tighter areas. That's one of the uh changes on the newer one. a little bit tighter areas. Okay, so when you're cutting copper and you're cutting your Edge this blade, it pushes into the copper in order to form that cut right. So then you have a little lip on the inside that curves over. and if you just stick that straight into your flare gun or your flare tool and you push that out, that lip gets smashed. Well, it's a point where there's going to be ridges and cracks. Now on the inside of your perfect flare, there's going to be ridges and cracks. And so it's a point that you can actually have leaks. So that's where the deburring tool comes in. You actually have to go in there and cut out that lip. Now, take your time on this, paying attention to what you're doing. If your copper is sitting like this and you start using the tool, you know little little bits are just going to fall straight down in there. So you want to adjust your copper to where it's got a little bit of a downward angle and usually there's a line set attach to it right, so a little bit of thought into that. Don't just move some. So as you're taking off that edge, you want a nice clean Edge In here, you don't want to get so much off that you actually create a thin spot on the copper. You're just taking that lip off. And then once it gets down to uh, where the rest of the copper is and you're done all right, it's also worth mentioning there's a couple different kinds. One looks like a little cone that you place in there and you twist and then ultimately if you don't, if you don't have one or whatever, you can actually use needle nose pliers and just Place those into the end and just kind of flatten out that. um, that? Burr I I Haven't had good luck with that, but a lot of really smart people do that so you know it's here. in a pinch, that's worth trying. Okay important, you actually need to have your flare nut on the copper before you do the flare or it won't slide on. Super frustrating and not backwards. You know what I mean Like this would work for this side, but I'm going to turn that around and with the Navac switch kit super easy. you slide it in and it has a little guard right here. It'll stop the copper as deep as it needs to go. and the reason for that is that you want your flare angle to actually match the nipple on the other side not to stick further out into the threads not to be so short that you don't actually have a lot of surface pushing together. so this actually has a guard on it, which is another reason why these are so great. So you have to push it against that guard and then you know you're at the right depth. tighten that down which is similar to when you're using in step four. On the illustration, it shows a guard on the manual one as well or uh, whatever you want to call it. Yeah, there's a stop there and that will kind of get you at the right path. Okay, so then I'm gonna go forward into the flare. you can hear when it's finished and then back that back out. If you want to make sure when you're backing it out, you take it all the way back. Another feature with a newer gun is you just push the button. It takes it all the way in and back out for you. You don't actually have to control it manually, that's the newer version. But and then your flare joint. Before you hook up your flare, you want to inspect your joint and actually make sure that it's beautiful and so you can just give that a visual inspection. you go around that top. Edge Don't have any lip that's been folded over and pushed in and cracked and it's smooth. and slide that up against the nipple that you're going to make sure that the width here, it covers the face of that. It's not sticking too far into where the threads are. it's not too short. and before you tighten down, you want to line this up perfectly so that the copper resting is sitting right on that nipple right where it should be instead of like pulling away. So as the years go by, the system's running and vibrating and that backward pressure is just pulling against there and it can crack the flare or pull it out, create a leak. so there's your flare making demonstration. A couple more points on that, a little helpful hints, adding a little bit of dialogue to uh to the threads or to the Copper keeps it from binding up and then uh, on the same topic of the proper tools to have you know, carrying a torque wrench and setting it to the proper specs. It's always nice. I Think we're all used to just give it the old field test, but uh, using the torque wrench is probably the better idea. It's not probably a better idea, it is the better idea. Oh, it is the better. Branch by Hillmore Couple things to mention: um Sam Said: placing it on the threads of the Um of the flare. really the back and face of the flare. the areas that you really want the most. A little bit on the threads is okay to act as an assembler assembly lubricant which is really what we're using it for. Here, it's not so much red sealant. A lot of people get confused. Nylog with things like true blue um or other types of thread sealants that Harden that's not what this is. This is not something you're going to buy at. Ace Hardware right? Depot This is a very specific product made by refrigerator made with refrigerant oil. It will affect your torque specs that always comes up. People always point that out. Um. But again, we've done it. We've used it for a long time and still continued to tighten this back and we have good luck with that. So another thing to mention. the torque wrench that's shown in the photo here is not a digital torque wrench. It's actually one that utilizes Um, gives its manual and so it just gets to the right torque and it does that clunk clunking motion. If you've ever used a traditional torque wrench, those also work perfectly fine. Um, that the one that's shown here is a yellow jacket that's designed specifically for flares. You can use a traditional torque wrench with a claw feature on it with a crow's foot connection on it, but you just have to make sure that you're not extending the length and so you would actually have it at 90 degrees the route Having it straight out that would extend the length and I should change this torque setting whereas this yellow jacket one is actually designed for that. So again, with the torque wrench, it's always really important that you hold it by the handle. If you change where you hold it, you're actually changing the pivot point and changing being at the end. Um, that you're that you're producing all right. And this is probably the number one reason that we get called out to just random ductless systems. You know there's a lot of people installing that they're all calling their maintenance guy to install a ductless system or something. and flares leaking are probably the number one reason we can call out to A Douglas system So system low, refrigerator Another no because some of some people will say like well, how do I this procedure looks good, but where do I find it later All of these procedures are available on the HVAC school app. If you've got an HVAC school app and you go into the part that says checklist checklist That's right, I forgot what it was called in my own app. Um, they have this here as well. so that's your app Christmas All right. Next, insulate, insulate, insulate. So one difference between a ductless unit and a regular split. Uh, regular split. You have your two copper lines from indoor to outdoor. One's insulated one is not, one is cold, one is not on a ductless unit. they are both cold. You have a suction line and you have the expansion line that run from the indoor to the outdoor or vice versa. The Exv is located inside your condensing unit, so on the other side of that, you have that liquid Vapor mix heading back to the indoor unit. And because both lines condensate, it's important to pay attention to any Nicks tears that may occur A lot of these time. The copper is running overhead through The attic and as you're pushing it, it's getting caught on roofing nails. You're opening it up to do a flare and connecting it. It's always important to remember to reinsulate the entire line from from beginning to end. Uh, no one wants water leaking up in their attic, so pay attention to that. That's a big one. Also, keep in mind, thumb gum and cork tape do not have the same insulation Factor as actual um, Armaflex or whatever tubing insulation, whatever you want to call it. So make sure that you have tubing insulation going all the way to the end. And when in doubt, wrap it with additional tubing insulation are sometimes multiple layers of foam tape can be used in place. But don't just pack thumb gum or cork tape around it and expect that to keep it from the condensation. Yeah, many, many service calls where we've gone out for something leaking and we haven't been able to pinpoint. You know exactly what's leaking. Is it the pump that's failing? Is it a connection point? A lot of the time it's just a small section of something that's getting to dew point and condensating water. It doesn't happen right away. A lot of these leaks happen over hours of run time, so if you're in that position, keep that in the back of your mind. Condensation pressure testing after you've made your perfect flare is still really crucial and important. So um, just actually getting the nitrogen up above 300 you know around 400 PSI is good because those flares are going to be in heat mode and that your PSI is going to be pretty high in heat mode on all those flare joints. And so you can. If you actually look at the data tag, they have your low side, high side pressure design pressure on here. so typically you want to go somewhere around the low side for pressure testing. but if you look at the manual, they'll often ask you to go even higher than that to test. Those flares. Put bubbles on them every time. So when you put bubbles on the flare, you do a nice smooth coating on that flare and you let it sit for a little while. If you don't see bubbles right away, you can come back to it and see if there's any active bubble action going on there on those joints. Now, oftentimes they're a little hard to get to the bottom side without a flashlight and a mirror, so always have your flashlight your mirror right there with your little bubbles. When you're testing that, and in the meantime the system is sitting, you're watching the PSI to making sure that making sure that it's not actually dropping under that pressure and then you're safe to go ahead and hook up the vacuum. Now, vacuums on a ductless system is such a small area, they'll pull down really quickly, which is great. That's nice you take out your Schrader core. The vacuum and the pressure testing is universal for like all the systems that we work on. so we didn't like develop a step-by-step slide for you guys on that. we have all of that in articles, videos, and HVAC School checklist so you can check that out. But best backing practices are really important. They people are buying these kits online sometimes and just hooking them up and putting them together and creating their own problems with their electronic expansion valves seizing up because there is moisture. There's crap inside the system. So yeah, a vacuum is still a really important step. and that DK test will also let you know it can be your guarantee that there's no issue with your flare joints. When it says high side and low side pressure, keep in mind this is a heat pump. Which means that everything that's outside that condenser is actually always going to be on the high side in heat mode. And so when you're pressurizing outside the equipment, that's why you can pressurize over 320. In fact, most manufacturers recommend it. You would not go over 600 PSI But again, remember the weak point on a system. Almost every system in terms of pressurization is actually the fusion plug on the compressor. The compressor shell is actually low pressure and that's what you don't want to pressurize to that higher pressure. So if you're pressurizing inside the condenser on The low side of the reversing valve I.E The compressor shell. You wouldn't want to pressurize that over 320. PSI But the rest of it has to be designed for the high side pressure because in heat mode, the indoor coil is the condenser. Does that make sense what I'm saying here? So in heat mode, that inside is going to see that high pressure anyway. so it is on the high side the system so they kind of. They kind of make it confusing with that. Um, another thing that I want to mention with bubble testing. Bert Talks about this a lot in other videos. When you are spraying bubbles on, you don't want to just spray willy-nilly and create a bunch of foam that then makes it difficult to tell. If you have leaks, you want to put it on very flat and then actually let it sit and look for those little micro bubbles. especially on selectors and flares. You know, really pay attention to your flares. Don't make sure we don't have leaks because you don't insulate and make sure that we don't have even tiny tiny leaks with fires. As far as uh, needing to add in your refrigerant, it is stamped right on the data tag on how to do that. Can't go by sub, cool or by pressures. Usually you do have to go by the line set length. So if we look at this data tag here, we can see the uh: if the liquid line exceeds 25 feet, we need to add 1.8 ounces of additional refrigerant for every five feet. So knowing how much line you're actually using is going to be important here and again. A reminder: These units do not hold a lot of refrigerant. This one only holds two pounds. so if you find yourself adding over a pound trying to get your your pressures to look good, something's wrong there. so make sure you slow down in this in this part of the process. Also, keep in mind your hoses can hold several ounces of refrigerant, so that alone can impact a critical charge like this. Yeah, you got a full tank, Your hose can hold like three ounces of refrigerant, and then you're manifold and maybe your other hose involved in the mix. You could. You could have more than you need just in your hoses, which is a reason why. I Don't like doing it how it's shown here with the big old gauge and multiple six foot hoses on it, because that makes it more difficult. I Would rather see us do it with the shortest possible hose probably one six foot hose or even four foot hose and a probe setup. So that way you're not, you're not having all that additional charge once you've bled your hoses, then reset your scale and you have that ball valve right there so you can open it up and you know anything happening on your scale is what's going in past that point. right? Then you shut the ball valve off and then you've saved the refrigerant that's in your hoses, so you're not worried about that extra refrigerant going into the system. Yeah, and then you won't be wasting extra refrigerant if you use a small line and just hook straight to the tank. But Aaron Ward has a question. So the the one big thing with finding and making sure you have good flares that I found out that really works is whenever you're doing a vacuum at that 10 minute isolation test is going to be the big factor. I mean Bubbles and all that work Really good. But to find those kind of really small leaks in your flares, that's going to be the biggest tell sign for it. Um, and also, and also whenever you're looking at trying to figure out how much to charge Mitsubishi is the only one that tells you on the data tag. so you're gonna have to read a manual if you're working on any of these. Yeah, and again, it's it's. actually, you know this is pretty basic math. Um, it's the amount of refrigerant that liquid line can hold um, per five feet. So you can actually use the charging calculator on my site as well. But but then you wouldn't necessarily know what the initial line length is for that manufacturer, so you're not probably going to get away with it with not reading that manual. but when in doubt you can, you can look it up on our app. Um, Chad says the micron gauge will always tell, which is also kind of supporting what Aaron said. For those of you who don't know how to do a proper Decay test, this is again where using less lines, only using a single vacuum hose, and then valving it off and seeing if it decays. That's that's really a good practice. Um, when you're doing vacuum, you want to have the minimum number of connections, the shortest possible hoses for vacuum, the largest hoses that you can have, and then that micron gauge. Seeing that decay is really going to tell you. if you don't know how to do a proper Decay test, Um, then you're going to get really frustrated. Just similar to what we talked about this today on doing a Decay test directly on your micron gauge. If you've ever tried to do that, have you ever tried to valve off a micron gauge with the ball valve and see what it does? The thing jumps Sky High in the matter of seconds. And it's not because there's anything wrong with the micron gauge, it's because there's such a tiny amount of internal volume that you're pulling a vacuum on in that case. So what we're saying is here: you take a little tiny hose with a little ball valve in your micron gauge. You hook it up to the pump, you pull it down real deep, you valve it off, and you see how quick your your micron gauge. Rises Just do it. Sometimes the thing will just go, it'll just go bananas on you. And it's because there's such a tiny internal volume and everything leaks. Every ball valve leaks, Every seal leaks, your micro engages, self leaks, Everything leaks. So the more volume that you have behind it, the less that is going to, the less that speed is going to be there. So the smaller the volume, um, the faster it's going to change. Which is why in ductless systems, if you have a ductless system that passes the 10 minute Decay test, it's pretty tight because the internal volume is so small. If you do the same test on a five ton unit, it's going to Decay less because there's more internal volume that you're pulling a vacuum. That makes sense, which is why on things like Vrf systems where you have you know, miles of copper tubing, they make you do multi-day pressure and Decay tests because there's so much internal volume that if you have a leak, you could have a hisser and it's not going to show up because there's so much nitrogen in that system if that makes sense over a shorter period of time. So in Douglas if you pass a pressure test, you pass a bubble test and you pass the Decay test. you don't have A leak. Now it could still leak later on because of a bad flare connection. Like we said, over time, they can still, uh, create leaks, gravity drains, and condensate pumps. Depending on the application, you'll be going with one of these two. If you're installing a wall mount on an exterior wall, the best thing to do is to install a gravity drain for a variety of reasons that we'll get into, but it's not always possible to do that. So in the case where you are on an interior wall, condensate pumps are going to be the next best option. They make a variety of pumps with different functions, but they all basically do the same thing: Water fills a reservoir, some type, it triggers a motor and pumps that water outside. So we have a couple of pumps here that we like to use a lot. We have the uh, the orange Aspen I believe it is here and also the white Aspen The orange Aspen is generally installed on the inside of the head unit. Here you can pull this unit slightly forward and it is installed up on top of the lip on the back side of the unit. And sometimes if we have a line set that comes off the unit, it can be installed in the line set as well. That is the reservoir location. The motor location can be inside the line set or in some cases it can be up in The attic itself. Um, now these motors do you know tend to make a noise. so you always want to be aware of location when installing these pumps. But uh, we'll get over the benefits of each one here. So the gravity drain benefits. We have less maintenance. We're no longer talking about a small Reservoir that gets filled up with Gunk we're talking about. you know, three-quarter inch pipe that's draining outside so less maintenance is needed on those. Less noise for obvious reasons. There's no pumps running on a gravity drain. Lower chance of water damage. You know these little knives are install installed various locations often above. Electronics Furniture Hardwood floors. so you don't have a chance of a pump failing then less chance of water spillage. So lower chance of that and they just generally look better. This unit here is installed with a gravity drain so you don't have any additional line height on it. You don't have a pump underneath the unit, so just for the aesthetic of it, it looks a lot better. So that's for the gravity drains. There benefits of the pump? None. No benefits really. I Mean if you don't you know you can install the the head in more places with a pump. However, it's basically the opposite of all this more maintenance. You're going to deal with the noise aspect of it when they fail. You do attend with a tend to have some some water leakage and uh, you're You're generally going to see something that comes with it, whether it be a pump sitting directly under the unit or some line hide going up into your attic. So placement of the head is important just because the drainage aspect of it. So a couple things here. Um, first off, when we do maintenance, you have to clean the reservoir. That's a big thing. Another thing is we usually use copper for the Um for the discharge. Uh, copper is highly conductive. The longest time we didn't really bother insulating them, but it's still cold water and so if there's any water standing in there, then in some cases it's not much because in many cases you're kind of pumping it up and then it's draining out periodically so it doesn't actually get cold and condensate. But we really should be insulating um, these drains uh as well as well because again, it just depends. You don't necessarily always have to, but it's a good best practice, especially if it's running through an attic that is a you know, 90 degree dew point in some cases. And another thing is, don't run chemicals through condos, don't run hardly any chemicals through opponents any pump. It's usually going to destroy them except the very most mild. And then even when you do, make sure you run fresh water through to clear them out. So like for us, using the EVAP plus properly diluted, you could run some of that through there, but I wouldn't even leave that in the in the recipe. It's just they're very sensitive to cleaners. We'll get a little more deeper into the actual maintenance side of things coming up here, so thank you! Brian All right so we've completed the installation done on all of our proper processes. The last part and a really important part is closing with the customer explaining full operation what to expect can avoid some unnecessary phone calls and unnecessary return trips. First one up here is just going to be the remote operation. We won't get into Super detail as far as the actual settings of them, but couple a couple key points on them. Um, one misconception is that the remote itself is what's measuring the temperature in the space because it's actually showing what it's set to. Um, that's not the case. however. Uh, this unit is actually measuring the temperature at the head, so you need to properly communicate that to the customer. A lot of the times they just like to fiddle with it and not actually point it at the unit. but it does use an infrared beam to control the unit and requires you to actually point it at the unit. So when it out, turn the unit off and turn it back on again to make sure it's still operating. Another one is the battery location of says remote. It requires you to pop the case completely off which reveals the batteries. I Believe they are two year run time on these batteries so every two years might start getting dim on. You might completely turn off. Got to replace them so knowing where that is important. Next thing up here is the blower operation. A common concern that comes up is that the blower never shuts off on these units, and that's the case with many ductless units. Now, as previously stated, the unit does measure temperature at the unit head, and in order to properly read that temperature, it continuously runs the blower motor circulating air past that sensor, in turn, constantly running that blower motor. So that's the design of the unit. If you want to shut off that blower, you have to shut down the unit completely. So that's a common question. Maintenance: You know, how often do you maintain the system? How often do you clean the filter? Well, we'll talk about that next. I'm not sure why we put that there, but maintenance is a question. and again I Want to say it again. Pump Noise: Whether we're out quoting the ductless, whether we're installing the ductless, having those conversations about the noise level of these pumps is important. The customer may say they it doesn't matter to them. However, a lot of these units are located in a room with the TV or a reading area or someplace. They just want to relax and when that pump kicks on every five minutes, it can get pretty loud. So properly installing them, there are some tips and tricks you can to quiet them down. Whether it's you know, putting the motor in a uh, a noise proof duct board box that we've seen helps a little bit with the noise. You want to be cautious of overheating the motors in some cases, so you know whether it's insulating it or hanging it, keeping it off trusses just to try to dampen that noise as much as possible. Always being aware of that and properly communicating it during installation. Aaron Ward has something else to add. Go ahead. Aaron Thank you! Um. I've noticed a lot when having to install. um, the pumps. They have a shut off and they like you to split the S wire and I've noticed that whenever you split the S wire and it's longer than about 40 and 50 feet, you run into a lot of communication problems with the unit. Um, so he has to keep that in mind when working with it and trying to find other ways for that. Automatic Pump Shut down when it's not draining to save water damage and how to get it to work differently. I've used it and changed it to cutting off power completely, but that's something that you really got to pay attention to. Yeah, so per the install manual of let's say the Orange Condensate Pump here, between the indoor and the outdoor unit, you have a three wire high voltage wire. you have two legs of 120 and you have a communication wire that the units communicate with. So per the manual, you want to actually break that communication wire with one of the gray or purple wires here. So that way if the pump were ever to clog up or potentially fail if that, Reservoir Rises to a certain level, it'll actually break the communication to the unit and shut it down. So what Aaron was saying is if the actual high voltage line is long enough, which is what I'm kind of understanding you were saying they can cause some random communication issues tripping that off. So keeping that in mind, it is a nice safety to have, especially in cases where the unit is above anything important. So in our application too Britton pointed this out to me earlier that you can tie your safety in with the dehumidostat because we are putting them in with dehumidostats actually there so that they are set up as dehumidifiers and people when people use them in their Lanai instead of actually a fully aced conditioned sealed space. and so you can break the wire from the hemitistat so it's just another option for breaking it so you could hook it straight into that. Okay, so that sort of wraps up the installation side of things. When you're uh, mounting a head unit, is it important to say you're say you're drilling through a block wall? Is it important to pitch that uh, hole? so the water drains from inside to outside? Yes, it's actually on our slide. Oh, it is. I Didn't see that though. Yeah. I didn't actually go over it. so that's probably why. Yeah. So whenever you are installing a unit on a exterior wall and you are looking at doing a gravity drain, having that whole pitched downwards going outside is important. Water flows downwards and you don't want it flowing inside the house. so pitch it downwards heading outside the house. and again, height restrictions inside is a big aspect of that. You know where you're going to put the unit. Always think ahead before actually cutting that hole. In order to service this, we got to be able to pull this off and raise this at an upward angle to unclip this. So if it's so tight right here that we can't actually get in above here and unclip the clippings, it's it. Can be a nightmare. Yeah, there's also a spec that gives you a minimum. Yeah, Um, yeah. I Got a good question? Yeah, how can we attach the drain line that comes with the unit to the outdoor? PVC Fantastic. Glad you asked. So we have a uh, we have the factory piping that comes with the unit for drainage. Uh, per the manual, they don't actually give you anything or show you anything on how to actually connect it to a pipe. However, the exterior of this insulation fits pretty snug into a regular three-quarter inch coupling. So what I would recommend is using some type of sealant, some kind of a waterproof caulking around the insulation and then inserting it tightly into a set coupling, letting that dry before you actually put any water through it. If you have a portable hot glue gun that works too, there's no exact right or wrong way to do it. However, anytime I've done that, it's solved any kind of leaking issues. But anytime you're working with any kind of drain connection points, spending extra time slowing down, making sure we're getting those two connections tight. Don't make any cuts on this pipe unless you know you have everything in place. What tends to happen is we make a cut and then go to connect it and find it's a little bit too short, can't quite fit it. you know, deep enough inside that coupling. So uh, just make sure everything's in the spot in place before you cutting anything. I'm glad you guys are here. I'm glad that all of you are going to be sticking around for the next 45 minutes to an hour for the maintenance section. Um, actually, maintenance on ductless systems can on a well-maintained system can actually go pretty quick. So less than a half hour as far as training goes on this, so we're gonna. we're gonna go for that. However, they're also notorious for becoming really nasty, so it's important to have regular maintenance keep them all clean once they get really gross. There's a lot of extra work that goes into cleaning them because they're so compact, right? So the things that can get nasty on them are the coils. That's where you get your your complaints about smell. The customer is smelling something when it comes on. It's typically there's some sort of algae growth happening inside the coils and the bib kit is perfect for that. You can actually use pressure cleaner and washing it out. Blowers: You guys have all seen the blowers. Gunk Up They get pretty nasty drains and pumps. Huge one. We're going to be going over each of these individually and the pans can Gunk up and they can actually clog at the little exit Port right where they hook up into the drain. right here. Um, and you have this build up that can happen over time and then break loose and just clog right there. So I've seen that several times. Cleaning out your pans. Important. So let's jump into all of these things. then. Um, the first step in every good maintenance is quality customer service. And so like Sam said, showing up you're in the customer's home. This is important to them and they need to feel recognized, heard, and that and see that you care about their space. You care about them. everything else that you do after that point. Whether you run into problems, whether you have an opportunity for some upgrade conversation with the customer, whatever it is, it's all going to go much smoother for you. when they actually trust you and see that you care so fake it. Ask the customer questions about their system. Okay, how's it working? How's the unit been working since we were out here last? Do you have any concerns? Uh, is there a problem that I need to know about before? I Get started on here. Always ask those questions even even though you would love to just go figure it out on your own. they need to be heard. But also understanding what their concerns are beforehand allows you to address them properly. So protecting a customer's home. Shoe covers, drop cloths, and the space. These are installed inside your interior space typically so you know the air handler might be in a garage or in a closet and you can feel more free on that maintenance. but this like you're in their personal space and it's right above. Typically stuff that can be damaged so be mindful of your surroundings. move customers things out of the workspace. Don't be sitting there doing a maintenance right over a couch. Okay, and that usually means that you're probably not using water or cleaners and stuff. Anyway, if you're not making a mess on somebody's couch or you're just a lot cleaner than I am I Pretty much always am making a mess. So move some stuff out of the way carefully not to break anything. Lay a drop cloth down in the workplace and this sets you out as someone who cares, as someone that can be trusted in their home and who's going to do a detailed job right there. So once that's done, you can wrap up, leave the customers home and customer service is what it's all about anyway. Hope for the best with the equipment. Foreign. That's a lie. I was just kidding. It's not all about that. it's not all about the show and this isn't a show. Come on guys care. Yeah, once you care, you're going to enjoy it. People don't care how much you know until hey, Philly see how much you care? no how much you care? Yeah, no I said it right when you say see how much you get it. Oh, until they know how much you care, you gotta use the no again. Okay, come on please. I'm trying. we're running. Go over the scope of work I Really like this on the maintenance because you add value to what you do. The customer might not be watching, but just quickly letting them know I'm going to be cleaning the drain or if there's a pump in the side. I'm going to be cleaning the pump. Let me clean the coils, checking over your equipment, adding value to what you do. Great move right there. All right. This is your maintenance process. Um, develop a process. Stick to the process, always deliver something like that. Um, pre inspect the equipment, so get eyes on everything. How does it look? Um, turn it on and actually make sure that your system's running. If you notice any issues, communicate with a customer before you start your cleaning process. So if I could just slide this over here, let's pre-inspect Let's just confirm operation non-invasively making sure the system's running and you're not seeing any red flags before you are opening the system and doing stuff that maybe the customer feels like hey, you just it was working great until you got here. I mean what'd you do? You know what I mean. So find out major issues that could be going on, communicate with the customer about them. if they're there. you got to shift gears to problem solving instead of cleaning. But typical maintenance, you pre-inspect you communicate any issues, you clean the system, you're always going to confirm again after you've cleaned and taken everything apart, that your system is operating the way that it should, and you communicate with the customer what you actually did in closing the call again. Important. Okay, so let's just go straight into testing system. Ductless system that's working well can be tested actually pretty easily. You're going to want to make sure that you turn the unit on into full stage so that the compressor is actually running full speed, and that's the only way to accurately check your readings. The easiest and most simple way. this is what I use on a maintenance to to know if your ductless system is working is to take a temperature split and you're typically going to be between 25 and 30 degrees and like, almost always 28 like it's It's a pretty consistent temperature split when you're dealing with normal temperatures inside the space. Um, obviously that can be different if the unit's been off and it's really humid and really hot. Again, on a typical on a regular AC system, our Target is at 20 right? Like? that's the rule of thumb that you always hear. But if you you've got a ductless running full speed and you got a 20 degree split, you have a problem with your charge. Something's actually going on. It should be closer to 27. degrees when we split, so you don't just have necessarily have just a problem with your charge. It could be other things and so the only issue would be your chart and it's leaking in the flare joint. No, yeah, I Feel like that's it? Okay, there are other potential problems. Uh, you'll have to call tech support for those. Um, always, just try adding refrigerant. Okay, um, as you're doing this, uh, run test on the equipment you're looking for red flags that would take you from your non-invasive check to actually needing to hook up to the system and check your refrigerant and check your superheat. Now if you're using probes, you're not going to lose a lot of refrigerant hooking up to the system, right? Especially if you have a proper, uh, straighter depressor tool on the end of that or a loss fitting. That's great. You can hook up to this, but typically when you're testing a mini split system, you don't want to hook up a gauge. You don't want to hook up manifolds and hoses. We've already talked about how much refrigerant that can hold you go and you service a system. You know, twice a year for three years and this thing's going to be low in refrigerant because we've been checking it every time. So a non-invasive test. We've got a great split. We don't have a reason to be concerned and the story from the customer is also that it's working good. Great Red Flags. This is when we're going to be hooking up. We have a warm suction line. Why is the low split? Oh it is on there. Low split. Uh, we have see ice forming on the expansion line now. I Have seen a system that's been sitting off for a really long time. You first turn it on, a little ice is there and within a couple minutes of run time. So as with everything else, you turn your system on. give it 10 minutes. Did I write that down? Wow. Give it 10 minutes to run before you check. So if you got ice on Your expansion line, the liquid line that comes up in the smaller line, that's a real clear indication that you are low on charge and it's actually starting to flash and freeze right after the expansion valve. Again, not necessarily only low on charge, you could have. So again, low on charge is the primary issue. Um, in the last 10 years it has been a electronic expansion valve. Like once or twice. So seriously, and there's no way to know that ever. It's impossible. Unless you do some tests right. or wait to charge out. Wait the charge out. Yeah, Okay, yeah, this is not a diagnostic. No. okay service, Call right? This is maintenance maintenance. Uh, another sign would be sloshing sounds at the air handler. Like when you first turn it on. you hear the refrigerant, not when you first turn it on, but when you're in there and you've turned on the system and you still hear this just sloshing going on in the refrigerant, That is a typical typical indication that you are low on charge on that side of your system. Okay, now it's time to clean. Um I Like to do run tests before. unless you've actually looked at the equipment. You see it's really dirty. It's filthy. That's going to affect your readings, right? You can't trust your readings anymore. We're changing our process. up. we're doing. We're just going to test operation, but then we're going to do all of our testing after we've cleaned right. But on your typical maintenance on a ductless system that's well maintained, Uh, let's do our run test before we take everything apart and do cleaning. It's just a Time Saver Okay, so wash your filters with water and your condenser coils don't typically get that dirty unless you're in an area of really high dust. Commercial applications Barn Animals like my dog who lays up against it gets real dirty. Dryer vents gets dryer vents, animals. Yeah. or in our dirty children. In your case. No, the dirty children do not get the condenser coils dirty. It just doesn't happen. Wow. Uh, only use cleaner on that coil if needed. If it's really impacted and you're not going to be able to get it clean, then use cleaners. a condenser coil cleaning and that's fine. but typically water rinsing through that, you can get it. You can get it clean. So then next you're going to be removing the air handler panel. Oh, this is my part. I Did this were we supposed to talk about that? Next thing we'll be removing the air handler panel when you're doing the maintenance for better access to what you're cleaning which would be your coil and also your drain pan, right? So let's do that and blower bill and blower wheel. What's a blowing No? I'm just kidding guys. Am I doing this? Or yes you are okay. Yeah, we're actually in a Time pinch. All right. So so we have little tabs on here that just slip out and then these veins are actually marked upper and lower on there so you can see where which one they go on that. Thankfully, they're level so you don't really know what upper and lower is, but on the back side there's a notch that only fits into one of them when you put it back in and then you slip it up in place and you push your uh already did that, push your tabs over. All right. All right. and the next part here down I'll do the stocking the next part here. So you have tabs that cover your screws. You pull them out. Some models will have screws here, others will have a couple extra screws on here. According to the manual, you want to pull the bottom out until these clips, um, unlatch. or they're at least free enough to be pulled out. Now one of my favorite things to do when actually pulling this is you take the cover plate off that. oh, it's already off the side. This cover plate unclips. We got a couple Clips here that pull out and then you can, uh, grab onto the bottom of this um plate. So down here we have a couple screws you're not or notches. You're not going to be able to see it with that, but there's two arrows here and it clips into the back plate in that spot. I Like to have use a little metal piece that I've bent uh to have a flat Edge Because some of these are so tight on the wall, you can't get your fingers behind to unclip that. But if you slide it up underneath here like this, then you can bring it along the wall and pull it off of that notch and then pull the air handler out a little bit and this can be a bit tricky. It's almost impossible to not look like a noob to the customer during that part, so like that one right there would have been. It's really tight against the wall. sometimes that can be pretty hard so that little tool helps. It sounds really noisy so something's breaking. Do you normally do it this way? No No. I I Went straight into the pump. Okay, uh. I I Forgot that we're actually taking the cover plate off and I haven't gone to my pump slide yet? Okay, so let's just take the cover plate off first. I'm sorry I I should have done the whole thing myself I Don't know why I asked for Sam's help I'm so sorry. First, we're taking off the cover plate. You just skipped over a pretty good part there. What'd you just do? Okay, so on the bottom is it just the screws have been taken out? It just pulls out on the bottom. Okay, just grab it and pull it out. Is that The party skipped door? Yeah, just grab it and pull it out Guys, You got everything about that. Thank you. So then you slide out like this and you'll start to hear the top on. Pop And then there's notches that it slips in like this. so you push down on the top to get it out a little bit further. Don't break it. You always feel like you are going to break it, but you won't. You'll never break it. See how loud that is? It is right? Yeah, don't jerk and look around insecure in a customer's home when you're doing this. Please confidence you're going to hear that every time gravity drains versus cleaning pumps. And I'm actually going to start on the cleaning pump side. I Know it's not typical for people to start on the right, but that's because once I've done some of this, we'll be pulling the unit apart more. So when you have a pump application, you're going to have the reservoir up underneath inside of this right here and it's going to be super tight to get to and cleaning it. About the only way to do that is that still unlocked to take the bottom off you guys. They have a nice little tool for this, a little flat end. so typically in order to do this you have to pull the air handler out slightly. Now if this connection is loose at all, which if the drain runs along sideways, which they often do when they're going into a pump, this is not a pump. The drain's going straight back and it can't really pull back on the air. Hand that, whereas with the pump, the drain comes along the back of this and hooks onto this and you have a little bit more room. Typically your lines come up here and a line hide that you've opened up and you can rock the air handler slightly back. And when you do that, then you pull the reservoir down and you let the air handler just sit like this and you have access to everything that you need to clean right there. So um, you literally didn't flip it from the back plate. That's what you intended to do. Yeah, Okay, okay, yeah. I've never seen this before. Okay, now you do have to get to get to that pump. There's no other way to get to it. You know, clip it from the back plate. Now, typically you only have to unclip it from the side. But like I said, this drain actually is a gravity fed drain. It's tight. So I've unclipped the top as well. On this side, just a little bit more just for demonstration. That's supposed to happen. What's back there? Foreign? That's the condenser unit that is on the other side of the wall. Um, yeah. Okay, so when you're actually doing this, you'll have this connection hooking up to the drain, which then comes and connects to the pan right here and so you'll want to actually clean that out as well now. I will personally bring a vacuum inside, hook up, flush my pan, flush this all out, I'll take a brush um, if it's gunky or nasty at all and push it up in there and try to get that clean. So anything that I can clean is going to extend the life of my pump. um, and help it operate better. So a pump often will fail because it's actually got so much junk built up that it's pulling in to the pump motor. And if you've ever taken one of these apart like it's a pretty small hole right there that everything's got to go through so it doesn't take a lot of algae or a hard chunk of something to clog it up. which is why in the reservoir when you're cleaning your Reservoir you also need to make sure that you are cleaning the screen. The news on here somewhere: Clean the screen which can be in here. A lot of reservoirs will have some sort of screen and that's to catch that algae. We're talking about some of the big chunks from damaging them, but if that gets clogged up and your water builds up, on this side, it starts leaking in the system. Your float's not actually coming up because this has gotten so clogged that water's not coming by That can throw off the function of your pump and the function is your floats in. Here it comes up, triggers the pump, turns it on, and then pumps it out through the tube on the other side. Now, if you're running into repeated pump issues or you've noticed that there's a lot of algae in your system, then I would recommend hooking up to your line that actually goes outside and blowing that out as well. So you're going to want to hook up. That and that could depend on application. If you have some motor that's in the Attic Only in a rare situation where I think my Line's clogged am I going into an attic and opening it up and pushing air through that but a lot of your pumps like in this application, I'll show you cleaniness as well. You have that all right here. So then your exit pipe right here just goes up, connects to Copper, then goes downhill from there outside, and so you can unhook from here and push nitrogen through to flush that out. A little bit better too. I Typically on a maintenance, I'm not doing that unless I'm seeing a lot of growth and nastiness and I'm worried that like I've turned my pump back on, it's going slow and I'm worried about something happening there. Usually that small line doesn't clog because the velocity, it actually has pressure. So pressurized lines rarely clog and the Deep the unpressurized lines. Yeah, and that's all before the pump and it builds up inside there and inside the reservoir. On this one, you have an accessible Reservoir that hangs down here. These are also your louder pumps. You can often clean this a lot easier and the maintenance is great on it. I Would Just when you put it back together, typically there's going to be some foam pads that are in place to help with the vibration noise. Make sure that after you've done your maintenance, it's going back in that edges aren't touching, something hard that's going to vibrate and foam's actually back in place. You're not making something worse by doing a maintenance right? Okay, so I think that's good on your pump cleaning. Make sure your float is right side back up. It's such a common problem. they went ahead and just put a sticker on this style. pump your float switch like this way. not this way so that it's not falsely tripping or not going off when it should. avoid using cleaners inside the pump when you're cleaning out the reservoir. Um. Brian Talked about this so we will move on. Gravity drains Simple. You guys know what to do there, right? Hook up a vacuum you dump water through. The only other thing I was going to point out on that is that your pants. You can actually remove the pans to clean them. So if there's a lot of junk that has built up on there, there's a clip on the back here where you're drain right there. so you pull that down and it slides out of the pan and so then uh, you can take this whole pan off of the system. So let's do that real quick. and they just unclip the little notches on the bottom and so there's your pan and then you can take this and clean it out. If it's so bad, where you have growth all in here, I'll just unhook it from the board right here and take it outside and spray it and get it really clean. This part does all of it. Yeah, yeah. so instead of leaving that hanging I'm gonna go ahead and do that. Okay, so uh, the next thing we're gonna talk about is, uh, Blower Wheel Cleaning. Now that we've gone over, uh, cleaning our drains, our pumps, uh, the blower Wheels can get pretty nasty and you guys have all experienced that. Um, dust builds up on there and then airflow starts becoming an issue. You can get freezing, you will sometimes be pulling freeze codes, but often the customer is going to have stuff spit into their space like little black bits that smell weird and you just don't got the airflow to push across the whole space and cool the whole room. So let's let's uh, demonstrate taking this this blower wheel off and cleaning it for you guys. Okay here we go again. Service manual will show you step by step what you need to do. We've already opened it up. I've demonstrated taking the pan out. There are three screws on this side. Let me go ahead and hang the unit up. So I don't have another accident on film or something Loud crashes, put the unit back in place. It's good, right? Well done, Good. painful sir. Oh my man always wanted to hear that. so that is a support for the side of the coil over here. On this side. these three screws and so you can actually take the coil framing that's holding the coil in place and pull it out and you'll need that little extra room to get your wheel out. The opposite end is still hooked up to Copper You still have all your copper tubing there. You don't just yank that around and start bending the copper that's going in there right? There is some give you know, a little bit of room to play around with there, but um, you know, let's not get crazy. All right. So your blower wheel is going to have it in all of its fins, a slot missing, and just, uh, rule of thumb, let's make sure power's already been turned off right? It's probably good. that's not a rule somewhere. back. Step one: I was gonna yeah before that. so rule thumb. Um, whenever you're working around a running system, these fins are moving reall

5 thoughts on “Ductless system install and maintenance”
  1. Avataaar/Circle Created with python_avatars Donald Allen says:

    Let's make sure the power is off 30 minutes after the unit is in pieces. 😆 😆😆 not a fan of the bib.

  2. Avataaar/Circle Created with python_avatars Tom Lech / LECH AIR CONDITIONING says:

    👍

  3. Avataaar/Circle Created with python_avatars Mr Green says:

    If you have add to the line set in order to reach the indoor unit should One flare it, or is it okay to braze?

  4. Avataaar/Circle Created with python_avatars Alfredo Romero says:

    Gracias por darnos de sus conocimientos.

  5. Avataaar/Circle Created with python_avatars Renante jose Siguiente says:

    thanks for the tips

Leave a Reply

Your email address will not be published. Required fields are marked *

This site uses Akismet to reduce spam. Learn how your comment data is processed.